Wireless Communication Systems
The HZDQ series is designed for bucket-wheel stacker-reclaimers, stockyards and mobile equipment within industrial plants, covering point-to-point and multipoint interlocking, network communications, IP telephony, video surveillance and wireless remote stations.
Wireless bridges connect the control room and mobile equipment for signal, network, voice and video transmission according to site requirements.
Electrical control systems
Product overview and applications
HZDQ wireless transmission interlocking control systems are intended for equipment with frequent travel and slewing, including bucket-wheel stacker-reclaimers at power plants, ports, mines, coking plants and metallurgical stockyards. Wireless bridges connect Ethernet-enabled controllers to carry equipment signals and live data. Interlocking signals, control networks, voice and video links are configured to suit each application.
May provide an alternative communications link where trailing cables fail or cabling is difficult. Replacement suitability depends on signal purpose, interlocking logic and equipment behaviour following a communications failure.
HZDQ product schemes

Point-to-point interlocking
A wireless bridge connects the control-room master cabinet and machine-side slave cabinet for digital and analogue signals. The sample diagram shows 14 DI, 10 DO, 2 AI and 1 AO per end. The antenna and wireless module are integrated for outdoor installation.

Point-to-multipoint interlocking
One master communicates with multiple machine-side slave stations. The sample lists 14 DI, 10 DO, 2 AI and 1 AO for the control cabinets and illustrates up to 30 slave stations. Actual station count and traffic load are confirmed for each project.

Machine network communications
Provides a TCP/IP link between the bucket-wheel machine and coal-handling control room where trailing-cable fibre is damaged or cabling is difficult. The sample describes an option for 1–4 IP cameras and one IP telephone; the combined traffic must be checked against available bandwidth.

Plant wireless IP telephony
Connects control-room and machine-side network switches and IP telephones over a wireless link for voice communication between stockyard equipment and the control room.

Plant wireless video monitoring
Links field cameras, PoE switches, a network video decoder and the control centre. The sample illustrates cameras at a tripper discharge point; channel count and video bitrate are confirmed for each project.

Wireless remote stations
For PLC upgrades or projects where the original supplier supports PLC program changes. Sample examples include Modicon 140-series and Schneider PLCs, Siemens S7-300/400 and ET200 remote modules. HaoZhuo supplies wireless hardware for this scheme; interfaces and programming responsibilities are agreed separately.
Sample technical parameters and configuration conditions
The following values describe configurations in the supplied product literature. They do not imply identical I/O counts, bandwidth or range across HZDQ-100 to HZDQ-600. Final specifications follow the selected model and agreed documents.
| Item | Sample information |
|---|---|
| System architecture | PLC controllers, wireless bridges, antennas and control cabinets; point-to-point or point-to-multipoint. |
| Signals and interfaces | DI/DO and AI/AO; reserved RS485 expansion interface. I/O counts are model-specific. |
| Wireless standard | IEEE 802.11 a/n (sample configuration). |
| Frequency and data rate | The sample lists 5170–5825 MHz and 54–108 Mbps; these are not guaranteed field throughput values. |
| Communication distance | Typical topology diagrams show 5 km; the overview lists 5–30 km. Actual coverage depends on antenna, line of sight, obstructions and interference. |
| Power supply | AC 220 V, power consumption <35 W for the sample system; wireless devices use PoE. |
| Enclosure | SUS304 stainless steel, enclosure IP65; 405 H × 515 W × 305 D mm, 9.5 kg for the sample control cabinet. |
| Operating environment | The product introduction lists -30 to +70 °C and 10%–95% RH, non-condensing. Confirm the operating limits of the selected components. |
I/O clarification: the series overview states “24 digital channels and 2 analogue channels”, whereas HZDQ-100/200 topology diagrams list “14 DI, 10 DO, 2 AI and 1 AO”. Use the model-specific signal list and approved drawings for selection.
Installation locations and interface confirmation
The HZDQ-100/200 sample places the master cabinet in the control room and the slave cabinet in the machine electrical room, with antennas and wireless modules outdoors. Ethernet cables connect wireless devices to PoE equipment, switches or controllers. Power, cable routing and wiring follow project drawings.
For selection, provide the machine travel path and site layout, distance and obstructions, DI/DO/AI/AO signal list, PLC models and network interfaces, voice/video traffic, installation space and power supply, and interlocking and recovery requirements following link loss.
Installation wiring, commissioning steps and acceptance requirements are confirmed in project technical documents.
Product literature
Compiled from HaoZhuo wireless communication system literature (HZDQ series, numbered pages 1–10) and the Shanghai HaoZhuo wireless product introduction. Diagrams come from the supplied product literature; historical application images are not evidence of delivery for a current project.